1 Valve mechanism activates in one second or less;it stays open until
manually closed.(Section 4.2, 5.2, 6.1.4, 6.2)
2 Be connected to a system capable supplying adequate flushing
fluid when all components are oprated simultaneously.(Section
4.5.5, 7.4.4)
3 Height of the flushing fluid column pattern shall be between
82"(208.3cm) and 96"(243.8cm) above floor.(Section 4.1.3, 4.5.4)
4 Watersupply shall be sufficient to supply at least 20GPM(75.7LPM)
for 15 mimutes.(section 4.1.2,4.5.5)
5 Valve actuator shall be located not more than 175.3cm(69") above
floor.(section 4.2)
6 The diameter shall be minimum of 50.8cm(20") at 152.4cm(60")
above floor.(section 4.1.4)
7 Center of the flushing fluid pattern shall be at least 16"(40.6cm)
from any obstruction.(Section4.1.4 ,4.5.4)
8 Water flow pattren shall be positioned between 33"(83.8cm) and
53"(134.6cm)from the level on which user stands and 6"(15.3cm)
minimum from the wall or nearest obstruction.(Section 5.4.4, 6.4.4)
9 Deliverd at least 3.0 gallons(11.4liters) of water per minute for
15-minute(Section 6.1.6,6.4.5)
10 Construted of materials that will not corrode in the presence of the
flushing fluid(Section 7.1.1, 7.1.2, 7.1.3)
11 Located 10 seconds or 55 feet from contaminants or hazardous
materials. Locate on the same level as hazard and free of
obstructions.(Section 7.4.2, B5)
12 Protect nozzle head from airborne contamination,dust covers shall
be removed by water flow immediately (Section 5.1.3,6.1.3)
13 Provided flushing fluid to both eye and face simultaneously at a
velocity low enough without injury to skin (Section 5.1.1,6.1.1)